Product information "Coolenvi™ PIV Cabinet Cooling System – 10.2 kW Sensible IT & Process Cooling"
The PIV MT 13125 precision cabinet cooling system is designed for reliable and energy-efficient climate control of small to medium-sized server, technical and electrical rooms. Downflow air discharge delivers conditioned air directly into a raised floor for uniform cold and hot aisle distribution.
Delivered as a fully tested plug-and-play solution, the unit connects to one or two outdoor condenser units, providing scalable performance for sensitive cooling loads.
Optimised airflow
- Top air return intake
- Downflow supply into raised floor
- Optional plenum for floor-level discharge without raised floor
High performance and flexibility
- Two cabinet sizes
- 6–26.0 kW sensible cooling with one outdoor unit
- 33.6–35.2 kW sensible cooling with two outdoor units
- Piping length up to 100 m
- Full front service access
Advanced climate functions
- Cooling only or optional cooling/heating/humidification
- Optional humidifying and dehumidifying
- SHR up to 93%
- Low-GWP refrigerant R32
Efficient fan technology
- EC plug fans with variable speed control
- Constant or load-based operation
- Optional constant airflow or raised-floor pressure control
- Energy-saving standby mode
Safety and monitoring
- Optional water leak detection
- Optional fire and smoke sensors
- Optional return air temperature and humidity sensors
- Optional BMS connectivity (RS485, TCP/IP, LonWorks)
- G4 filter with differential pressure monitoring
- Priority A/B alarm outputs
- BlackBox fault diagnostics
Control and integration
- On-board clear text display
- Supply or return air temperature control
- Main switch and remote on/off contact
- Pre-installed interface card
- Cascade operation up to 15 units
A precise, efficient and easily integrated solution for mission-critical IT environments requiring stable temperature and humidity.
| PIV - Consumption kW: | 3.410 |
|---|---|
| PIV - Energy Class: | - |
| PIV - Height Difference (max.) m: | 30 |
| PIV - Pipe Length (min.-max.) m: | 3 - 100 |
| PIV - Refrigerant: | R32 |
| PIV - Sensitive Cooling Capacity kW: | 10.2 (SHR 0.86) |
| PIV - Nominal Cooling Capacity kW: | 11.90 |
| PIV - Nominal Heating Capacity kW: | - |
| PIV - Power Supply V/Ph/Hz: | 380-415/3/50 |
| PIV - Sound pressure level dB(A): | I 61 - O 50 |
| PIV - Pipe dimension mm (inch) / m: | 9.5 (3/8) - 15.9 (5/8) / 3 - 50 |
| PIV - IU Dimensions (HxWxD) mm: | 1980 x 600 x 500 - SG |
| PIV - OU Dimensions (HxWxD) mm: | 870 x 1100 x 460 - 125 |
| PIV - Room Size m² - (kW | BTU): | 100 - (10.0 | 34.100) |
| PIV - Weight IU/OU kg: | 110 / 116 |