Air duct construction, fittings & industrial engineering
Coolenvi™ supplies precision-manufactured air duct components, fittings and special construction solutions for modern ventilation and ducting systems. The range includes standardised and custom solutions for building services, industrial applications, process air systems, data centres, clean rooms and energy-efficient HVAC systems. In addition, components for industrial applications, containment trays for media and groundwater protection, and metal construction solutions ensure safe, airtight and standards-compliant media handling.
Comparison of Airtightness Classes for Air Duct Systems
| DIN EN 16798-3 | DIN EN 13779 | Leakage Formula (l/s·m²) |
Example +500 Pa |
Example −500 Pa |
Example +1,000 Pa |
Example −1,000 Pa |
|---|---|---|---|---|---|---|
| ATC 5 | A (Standard) | 0.027 × p0.65 | 1.53 | 1.53 | 2.41 | 2.41 |
| ATC 4 | B (Recommended) | 0.009 × p0.65 | 0.51 | 0.51 | 0.80 | 0.80 |
| ATC 3 | C (Special applications) | 0.003 × p0.65 | 0.17 | 0.17 | 0.27 | 0.27 |
| ATC 2 | D (Grease-tight, watertight) | 0.001 × p0.65 | 0.06 | 0.06 | 0.09 | 0.09 |
| ATC 1 | – | 0.00033 × p0.65 | 0.02 | 0.02 | 0.03 | 0.03 |
Note: Leakage rates apply equally to positive and negative pressure testing. The absolute value of test pressure p [Pa] is decisive. Actual test pressures are project-specific.
Insulation for Air Duct Construction